ON-VEHICLE INSPECTION

This is a method in which the trouble is located by using a gauge set. Read the gauge pressure when these conditions are established.

TEST CONDITIONS

Temperature at the air inlet with the switch set at RECIRC is 30~35°C (86~95°F)

Engine running at 1,500rpm

Blower speed control knob on "4" position

Temperature control knob on "COOL" position

note

It should be noted that the gauge indications may vary slightly due to ambient temperature conditions

1.

Normally functioning refrigeration system.

Gauge reading :

Low pressure side :

0.15~0.25 MPa (21.8~36.3 psi, 1.5~2.5 kgf/cm²)

High pressure side :

1.37~1.57 MPa (199~228 psi, 14~16 kgf/cm²)

2.

Moisture present in refrigeration system.

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

During operation, pressure on low pressure side sometimes become a vacuum and sometime normal

Moisture entered in refrigeration system freezes at expansion valve orifice and temporarily stops cycle, but normal state is restored after a time when the ice melts

Drier in oversaturated state

Moisture in refrigeration system freezes at expansion valve orifice and block circulation of refrigerant

-

Raplace drier

-

Remove moisture in cycle through repeatedly evacuating air

-

Evacuate the system and charge new refrigerant to specified amount.

3.

Insufficient cooling

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Pressure low on both low and high pressure sides

Insufficient cooling performance

Gas leakage at some place in refrigeration system

Insufficient refrigerant in system

Refrigerant leaking

-

Check for gas leakage with gas leak detector and repair if necessary

-

Charge proper amount of refrigerant

-

If indicated pressure value is near 0 when connected to gauge, create the vacuum after inspecting and repairing the location of the leak

4.

Poor circulation of refrigerant

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Pressure low in both low and high pressure sides

Frost on tube from receiver to unit

Refrigerant flow obstructed by dirt in drier

Condenser clogged

Replace drier

5.

Refrigerant does not circulate

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Vacuum indicated on low pressure side, very low pressure indicated on high pressure side

Frost or dew seen on piping before and after receiver/drier or expansion valve

Refrigerant flow obstructed by moisture or dirt in refrigeration system

Refrigerant flow obstructed by gas leakage from expansion valve

Refrigerant does not circulate

-

Check expansion valve

-

Clean out dirt in expansion valve by blowing with air

-

Replace drier

-

Evacuate the system and charge new refrigerant to specified amount.

-

For gas leakage from expansion valve, replace expansion valve

6.

Refrigerant overcharged or insufficient cooling of condenser

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Pressure too high on both low and high pressure sides

Unable to develop sufficient performance due to excessive

Insufficient cooling of condenser

Excessive refrigerant in cycle → refrigerant overcharged

Condenser cooling → condenser fins clogged or condenser fan faulty

-

(1) Clean condenser

-

(2) Check cooling fan with fluid coupling operation.

-

(3) If (1) and (2) are in normal state, check amount of refrigerant.

Evacuate the system and charge new refrigerant to specified amount.

7.

Air present in refrigeration system

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Pressure too high on both low and high pressure sides

The low pressure piping hot to the touch

Air entered in refrigeration system

Air present in refrigeration system

Insufficient vacuum purging

-

Check compressor oil to see if it is see if it is dirty or insufficient

-

Evacuate the system and charge new refrigerant to specified amount.

8.

Expansion valve improperly

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Pressure too high on both low and high pressure sides

Frost or large amount of dew on piping on low pressure side

Trouble in expansion valve

Excessive refrigerant in low pressure piping

Expansion valve opened too wide

-

Check expansion valve

-

Replace if defective

9.

Defective compression compressor

Symptom seen in refrigeration system

Probable cause

Diagnosis

Remedy

Pressure too high on low and high pressure sides

Pressure too low to on high pressure side

Internal leak in compressor

Compression defective

Valve leaking or broken sliding parts

Repair or replace compressor

INSPECT FOR LEAKAGE OF REFRIGERANT

Always conduct a leak test with an electronic leak detector whenever leakage or refrigerant is suspected and when conducting service operations which are accompanied by disassembly or loosening or connection fittings.

note

In order to use the leak detector properly, read the manual supplied by the manufacturer.

1.

Check the torque on the connection fittings and, if too loose, tighten to the proper torque. Check for gas leakage with a leak detector.

2.

If leakage continues even after the fitting has been tightened, discharge the refrigerant from the system, disconnect the fittings, and check their seating faces for damage. Always replace, even if the damage is slight.

3.

Check the compressor oil and add oil if required.

4.

Charge the system and recheck for gas leaks. If no leaks are found, evacuate and charge the system again.

REFRIGERANT RECOVERY
caution

Air conditioning refrigerant or lubricant vapor can irritate your eyes, nose, or throat.

Be careful when connecting service equipment.

Do not breathe refrigerant or vapor.

1.

Connect a R-134a refrigerant recovery/recycling/charging station (A) to the high-pressure service port (B) and the low-pressure service port (C), as shown, following the equipment manufacturer's instruction.

2.

Measure the amount of refrigerant oil removed from the A/C system after the recovery process is completed. Be sure to put the same amount of new refrigerant oil back into the A/C system before charging.

SYSTEM EVACUATION
caution

Air conditioning refrigerant or lubricant vapor can irritate your eyes, nose, or throat.

Be careful when connecting service equipment.

Do not breathe refrigerant or vapor.

1.

When an A/C System has been opened to the atmosphere, such as during installation or repair, it must be evacuated using a R-134a refrigerant recover/recycling/charging station (If the system has been open for several days, the receiver/dryer should be replaced, and the system should be evacuated for several hours.)

2.

Connect a R-134a refrigerant recovery/recycling/charging station(A) to the high-pressure service port(B) and the low-pressure service port(C), as shown, following the equipment manufacturer's instruction. Evacuate the system.

3.

If the low-pressure does not reach more than 93.3 kPa(700 mmHg, 27.6 in.Hg) in 15 minutes, there is probably a leak in the system. Partially charge the system (see page HA-24), and check for leaks (see page HA-22).

SYSTEM CHARGING
caution

Air conditioning refrigerant or lubricant vapor can irritate your eyes, nose, or throat.

Be careful when connecting service equipment.

Do not breathe refrigerant or vapor.

1.

Connect a R-134a refrigerant recover/recycling/charging station (A) to the high-pressure service port (B) and the low-pressure service port (C), as shown, following the equipment manufacture's instructions.

2.

Add the same amount of new refrigerant oil to the system that was removed during recovery. Use only ND-OIL8 refrigerant oil.

3.

Charge the system with the specified amount of R-134a refrigerant. Do not overcharge the system; the compressor will be damaged.

Refrigerant capacity : 510 ± 25g

Яндекс.Метрика