GAUGE READINGS | OTHER SYMPTOMS | DIAGNOSIS | CORRECTION |
![]() | ● Discharge air : slightly cool. ● Thermostatic switch (with thermistor) : Low side gauge doesn't fluctuate with "ON" and "OFF". | Some air and moisture in system. | ● Check for leaks. ● Discharge refrigerant from system. ● Repair leaks as located. ● Evacuate the system for at least 30 minutes. ● Charge system with refrigerant. ● Operate system and check performance. |
![]() | ● Discharge air : Becomes warm all the time during hot part of day. | Some air and moisture in system. | ● Discharge refrigerant. ● Evacuate system with a vacuum pump. ● Recharge system to proper capacity. ● Operate system and check performance. |
![]() | ● Compressor : Cycles on and off too fast. | Defective thermostatic switch. | ● Replace thermostatic switch. ● Operate system and check performance. |
![]() | ● Compressor : Low side pressure builds too high before compressor turns on (cycle "ON" point too high). | Faulty thermostatic switch. | ● Replace the thermostatic switch. ● Operate system and check performance. |
![]() | ● Discharge air : Slightly cool. | System slightly low on refrigerant. | ● Check for leaks. ● Discharge refrigerant. ● Repair leaks. ● Evacuate system using a vacuum pump. ● Charge system with refrigerant. ● Operate system and check performance. |
![]() | ● Discharge air : Warm | ● System very low on refrigerant. ● Possible leak in system. | ● Check for leaks. ● Discharge refrigerant. ● Evaporate system using a vacuum pump. ● Charge system with refrigerant. ● Operate system and check performance. |
![]() | ● Discharge air : Slightly cool. ● Expansion valve : Frost build up. | ● Expansion valve stuck. ● Screen plugged. ● Sensing bulb malfunction. | ● Discharge system. ● Disconnect inlet line at expansion valve and remove and inspect screen. ● Replace screen and reconnect inlet line. ● Evacuate system using a vacuum pump. ● Charge system with refrigerant. |
![]() | ● Discharge air : Slightly cool. ● High side pipe : Cool and also shows moisture or frost. | Restriction in high side of system | ● Discharge system. ● Evacuate system using a vacuum pump. ● Charge system with refrigerant. ● Operate system and check performance. |
![]() | ● Compressor : Noisy | Compressor malfunction | ● Disassemble compressor. ● Inspect compressor. ● Check compressor oil level. ● Operate system and check performance. |
![]() | ● Discharge air : Warm ● High side pipe : Very hot | ● Faulty condenser. ● Overcharged. | ● Check for loose or worn fan belt. ● Inspect condenser for clogged air passage. ● Check for refrigerant overcharge. ● Operate system and check performance. |
![]() | ● Discharge air : Slightly cool. | Large amount of air and moisture. | ● Discharge refrigerant from system. ● Evacuate system using vacuum pump. ● Charge system with refrigerant. ● Operate system and check performance. |
![]() | ● Discharge air : Warm ● Evaporator : Moisture or frost. | Expansion valve stuck. | ● Discharge system. ● Replace expansion valve. ● Evacuate system using vacuum pump, then recharge system with refrigerant. ● Operate system and check performance. |