DIAGNOSIS

GAUGE READINGS

OTHER SYMPTOMS

DIAGNOSIS

CORRECTION

●

Discharge air : slightly cool.

●

Thermostatic switch (with thermistor) : Low side gauge doesn't fluctuate with "ON" and "OFF".

Some air and moisture in system.

●

Check for leaks.

●

Discharge refrigerant from system.

●

Repair leaks as located.

●

Evacuate the system for at least 30 minutes.

●

Charge system with refrigerant.

●

Operate system and check performance.

●

Discharge air : Becomes warm all the time during hot part of day.

Some air and moisture in system.

●

Discharge refrigerant.

●

Evacuate system with a vacuum pump.

●

Recharge system to proper capacity.

●

Operate system and check performance.

●

Compressor : Cycles on and off too fast.

Defective thermostatic switch.

●

Replace thermostatic switch.

●

Operate system and check performance.

●

Compressor : Low side pressure builds too high before compressor turns on (cycle "ON" point too high).

Faulty thermostatic switch.

●

Replace the thermostatic switch.

●

Operate system and check performance.

●

Discharge air : Slightly cool.

System slightly low on refrigerant.

●

Check for leaks.

●

Discharge refrigerant.

●

Repair leaks.

●

Evacuate system using a vacuum pump.

●

Charge system with refrigerant.

●

Operate system and check performance.

●

Discharge air : Warm

●

System very low on refrigerant.

●

Possible leak in system.

●

Check for leaks.

●

Discharge refrigerant.

●

Evaporate system using a vacuum pump.

●

Charge system with refrigerant.

●

Operate system and check performance.

●

Discharge air : Slightly cool.

●

Expansion valve : Frost build up.

●

Expansion valve stuck.

●

Screen plugged.

●

Sensing bulb malfunction.

●

Discharge system.

●

Disconnect inlet line at expansion valve and remove and inspect screen.

●

Replace screen and reconnect inlet line.

●

Evacuate system using a vacuum pump.

●

Charge system with refrigerant.

●

Discharge air : Slightly cool.

●

High side pipe : Cool and also shows moisture or frost.

Restriction in high side of system

●

Discharge system.

●

Evacuate system using a vacuum pump.

●

Charge system with refrigerant.

●

Operate system and check performance.

●

Compressor : Noisy

Compressor malfunction

●

Disassemble compressor.

●

Inspect compressor.

●

Check compressor oil level.

●

Operate system and check performance.

●

Discharge air : Warm

●

High side pipe : Very hot

●

Faulty condenser.

●

Overcharged.

●

Check for loose or worn fan belt.

●

Inspect condenser for clogged air passage.

●

Check for refrigerant overcharge.

●

Operate system and check performance.

●

Discharge air : Slightly cool.

Large amount of air and moisture.

●

Discharge refrigerant from system.

●

Evacuate system using vacuum pump.

●

Charge system with refrigerant.

●

Operate system and check performance.

●

Discharge air : Warm

●

Evaporator : Moisture or frost.

Expansion valve stuck.

●

Discharge system.

●

Replace expansion valve.

●

Evacuate system using vacuum pump, then recharge system with refrigerant.

●

Operate system and check performance.