REPLACEMENT
1.

Discharge refrigerant from refrigeration system (Refer to HA-8).

2.

Replace faulty tube or hose.

caution

Cap the open fittings immediately to keep moisture or dirt out of the system.

3.

Tighten joint of bolt or nut to specified torque

caution

Connections should not be torque tighter than the specified torque.

Part tightened

N·m

Kgf·m

lbf·ft

Condenser - Discharge hose

5~7

0.5~0.6

3.7~5.2

Condenser - Liquid tube

Compressor - Discharge hose

Compressor - Suction hose

Expansion valve - Evaporator

12~15

1.2~1.5

8.7~10.8

4.

Evacuate air in refrigeration system and charge system with refrigerant (Refer to HA-9).

Specified amount: 500 ± 25g

5.

Inspect for leakage of refrigerant.

Using a gas leak detector, check for leakage of refrigerant (Refer to HA-9).

6.

Inspect A/C operation.