Component Location
General Description

The mode control actuator mounted on heater unit adjusts position of mode door by operating Direction Motor in accordance with signal of A/C control unit. Pressing mode select switch makes the mode control actuator shift in order of vent→ B/L → floor → mix.

DTC Description

The ECM sets DTC B2417 if the direction(VENT) motor dosen’t move to intended position within 40sec(The ECM attempts to move the temp door for a 2 second duration at a frequency of 3 times every 20 seconds before storing a DTC.)

DTC Detecting Condition

Item

Detecting Condition

Possible Cause

DTC Strategy

● Voltage check

● Poor connection of connected part

● Open circuit in harness

● Short circuit in harness

● Faulty DR Direction(VENT) actuator

● Fault A/C Control Unit

Threshold value

● < 0.1V

Detecting time

● 0.3sec

FAIL SAFE

● Setting mode : VENT

Fix at VENT position

● Setting mode : Except VENT

Fix at DEF position

Schematic Diagram
Signal Waveform

※ Voltage value of Air Mix potentiometer as a function of temp door position.

Door position

Voltage

Error Detecting Condition

VENT

0.3±0.15V

Undervoltage : 0.10V or less

DEF

4.7±0.15V

Overvoltage : 4.92V or more