The mode control actuator is mounted at the heater control unit. The mode control actuator consists of a motor and a feedback potentiometer. Pressing mode select switch makes the mode control actuator shift in order of vent→ B/L → floor → mix.
Air conditioner Control Module sets DTC B1250 if Feedback signal of Mode Actuator has been detected over 4.9V for 100ms.
Item  | Detecting Condition  | Possible Cause  | 
DTC Strategy  | 
										•
									 Voltage check  | 
										•
									 Short in signal circuit(Feedback signal) 
										•
									 Faulty Mode Actuator 
										•
									 Faulty Air conditioner Control Module  | 
Enable Conditions  | 
										•
									 IG KEY ON  | |
Threshold value  | 
										•
									 Feedback signal of Mode Actuator has been detected over 4.9V for 0.3 seconds  | |
Failsafe  | 
										•
									 If the Mode actuator is placed at Vent mode right before fail detection, Actuator is operated and fixed to Vent Mode Postion. 
										•
									 In case of the others, Actuator is moved to DEF mode position  | 
Mode Door Position  | Voltage  | 
VENT  | 0.4±0.3V  | 
BI-LEVEL  | 1.45±0.3V  | 
FLOOR  | 2.5±0.3V  | 
MIX  | 3.55±0.3V  | 
DEF  | 4.6±0.3V  |