Self Diagnosis
1.

Self-diagnosis process

2.

How to read self-diagnostic code

After the display the panel blinks three times every 0.5 second, the corresponding fault code blinks on the setup temperature display panel every 0.5 second and will show two figures. Codes are displayed in numerical format

Fault codes are displayed in numerical format.

Display

Fail description

0

Normal

11

In-car sensor open

12

In-car sensor short

13

Ambient temperature sensor open

14

Ambient temperature sensor short

17

Evaporator temperature sensor open

18

Evaporator temperature sensor short

19

Temperature door potentiometer open/short (Driver)

20

Temperature door potentiometer fault (Driver)

21

Mode door potentiometer open/short

22

Mode door potentiometer fault

23

Auto defogging sensor open

24

Auto defogging sensor short

25

Intake door potentiometer open/short

26

Intake door potentiometer fault

32

Temperature door potentiometer open/short (Passenger)

33

Temperature door potentiometer fault (Passenger)

45

APT (A/C Pressure Transducer) CAN signal fault

47

RPM CAN signal fault

48

Vehicle speed CAN signal fault

49

Engine coolant temperature CAN signal fault

50

Cluster ionizer fault

51

Dent sensor vent open

52

Dent sensor vent short

53

Dent sensor floor open

54

Dent sensor floor short

3.

Fault code display

(1)

Continuance operation : None or one DTC code.

(2)

Continuance operation : Two or more DTC code.

(3)

STEP operation

A.

Normal or one fault code is same as a continuance operation.

B.

There are two or more DTC code.

4.

If fault codes are displayed when checking, inspect for malfunction causes by referring to fault codes table.

5.

Fail safe

(1)

In-car temperature sensor : Control with the value of 25°C(77°F)

(2)

Ambient temperature sensor : Control with the value of 20°C(67°F)

(3)

Evaporator temperature sensor : Control with the value of -2°C(28.4°F)

(4)

Water temperature sensor : Control with the value of -2°C(28.4°F)

(5)

Temperature control actuator (Air mix potentiometer) :

If temperature setting is 15°C~22.5°C(59°F~72.5°F), fix at maximum cooling position.

If temperature setting is 23°C~30°C(73.4°F~86°C), fix at maximum heating position.

(6)

Mode control actuator (Direction potentiometer) :

Fix vent position, while selecting vent mode.

Fix defrost position, while selecting all except vent mode.

(7)

Intake control actuator :

Fix fresh position, while selecting fresh mode.

Fix recirculation position, while selecting recirculation mode.

(8)

Auto defog sensor : Control with the value of 0%.