Componet Location
General Description

The mode control actuator mounted on heater unit adjusts position of mode door by operating Direction Motor based on signal of A/C control unit. Pressing mode select switch makes the mode control actuator shift in order of vent→ B/L → floor → mix.

DTC Description

DTC B1250 sets if Mode Actuator sensor signal is at or over 4.9V for 0.3 seconds.

DTC Detecting Condition

Item

Detecting Condition

Possible Cause

DTC Strategy

Voltage check

1.

Short in signal circuit(Feedback signal)

2.

Faulty Mode Actuator

3.

Faulty Air conditioner Control Module

Enable Conditions

Ignition ON

Threshold value

Mode Actuator sensor signal is at or over 4.9V for 0.3 seconds

Failsafe

If the Mode actuator is placed at Vent mode right before fail detection, Actuator is operated and fixed to Vent Mode Postion.

In case of the others, Actuator is moved to DEF mode position

Specification

※ Voltage value of potentiometer as a function of mode door position.

Mode Door Position

Voltage

VENT

0.3±0.15V

BI-LEVEL

1.4±0.4V

FLOOR

2.5±0.4V

MIX

3.6±0.4V

DEF

4.7±0.15V

Diagnostic Circuit Diagram